One fix, 80% less HVAC energy at Wigan Civic Centre
Once cosmOS got Civic's HVAC data out of the BMS, one change cut HVAC energy by 80%, saving about 17,000 kWh and 3 tonnes of CO₂e a month.
Nemiah's cosmOS platform cut HVAC energy by 80% at Civic, the former Wigan Civic Centre on Millgate, after revealing that heating and ventilation were running when the building was empty. Changing when the plant operates now saves about 17,000 kWh and 3,000 kg CO₂e each month, compared to the November baseline.
Civic opened in 1970 as Wigan's local government base. After standing empty for years, Capital&Centric restored it and reopened it in September 2025 as a workspace, studios, a café, and a roof terrace. The project kept its brutalist style and earned a BREEAM Excellent rating.
The roof terrace at Civic, reopened by Capital&Centric in September 2025.
The data was locked in the BMS
Like most commercial buildings, Civic's HVAC is managed by a building management system (BMS). The BMS worked, but its data wasn't easily accessible. Staff couldn't easily check if the plant was running when the building was empty, and energy bills only showed totals, not reasons.
cosmOS was connected in 2025, bringing three key things together in one place:
- Metering: real-time readings for the whole 2,500 m² building, installed at the distribution board
- HVAC: data read out of the BMS, where it had been locked
- Billing: energy costs tied to the readings, with an integration into the accounting software
No equipment was replaced, and no new controls were added.
Installing cosmOS at the distribution board.
One fix
With all the data together, cosmOS's AI noticed the HVAC was running when the building was empty. The dashboard showed the same pattern: each day, the plant ran whether the building was used or not.
We made one change: now, the HVAC only runs when the building is in use.
Against the November baseline:
- 80% less HVAC energy.
- About 17,000 kWh less energy each month, compared to the building's total of 29,500 kWh in November.
- About 3,000 kg CO₂e less carbon each month, compared to the building's total of 5,200 kg CO₂e.
How HVAC ran at Civic through one day: before the fix, it ran whether the building was empty or in use. After the change, it only ran while the building was in use.
A good building still needs watching
A BREEAM rating shows how well a building was designed, but it doesn't reveal if the ventilation is running at 3am on a Sunday. That gap between design and daily operation is where much energy is lost, in both new and restored buildings.
The savings at Civic didn't come from new hardware. They came from seeing what the existing plant was doing. This is our approach everywhere: get visibility first, then act on evidence. We used the same method at Leigh Spinners Mill, and it's how cosmOS cut energy use at our own site, Leigh Works, by 65%.
This project is also close to home for us. Nemiah is based at Leigh Works on Bradshawgate, just a few miles from Millgate. We're proud to see a Wigan borough landmark set a standard for running a restored building.
"Civic is a beautifully restored building with a BREEAM Excellent rating, and it was still heating and ventilating empty rooms. That wasn't because anyone was doing their job badly: the information was sitting in the BMS where nobody could see it. Once it was in cosmOS, it took one change to fix. We see this pattern again and again. The savings are usually already in the building, waiting to be found."
Steven Tomlinson, CEO at Nemiah
Read the full Wigan Civic Centre case study at cosmos.energy.
Curious about what your building does when no one's there? Get in touch.